Combustion Controller BC-R for Intermittent Operation
- Combustion controller BC-R15/25/35 is a combustion safety controller specially used for intermittent operation (a device that starts and stops more than once within 24 hours).
- Automatic proportional control of fuel burner or gas burner ignition, flame monitoring, and fuel cutoff ensures safety. In addition, it has a 7-segment display that can be used during maintenance and a test operation mode that is convenient for test operation and adjustment.
Specialty
Combustion controller BC-R15/25/35 is a combustion safety controller specially used for intermittent operation (a device that starts and stops more than once within 24 hours).
Automatic proportional control of fuel combustion or gas combustion ignition, flame monitoring, and fuel cutoff ensures safety. In addition, it has a 7-segment display that can be used during maintenance and a test operation mode that is convenient for test operation and adjustment.
In addition, this machine is equipped with upper-level communication (RS-485)/intelligent programming software package function, which can carry out more detailed status monitoring and troubleshooting. (BC-R25/35 only)
Safety
Corresponds to the JIS standard that integrates international standards
The pre-purging and ignition time that is compatible with JIS B 8407:2012 (forced draft burner) and JIS B 8415:2008 (safety general rules for industrial combustion furnaces) are realized. Contribute to the safe construction of combustion equipment and combustion equipment.
visible
Combustion sequence, alarm content "main body visible"
The combustion sequence is displayed with 7 segments. In addition, the flame voltage can also be displayed by pressing the DISP switch.
When an alarm occurs, the alarm code corresponding to the combustion sequence is displayed in 7 segments. Alarm content is visible.
know
"Operating status at a glance" of the combustion controller
The monitor output outputs "no fire" and "fire break" respectively, and the alarm status can be easily known.
were able
"Easy adjustment" of combustion in test mode
Monitor output can be forced. It is convenient to confirm the lighting of the control panel or check the wiring.
The full open and full close of the motor can be controlled by forced output, and the adjustment of the high combustion position and the low combustion position and the air volume can be confirmed. (BC-R35 only)